datAInsights CVE Current

CVE-2022-33175

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyon…

Published: 2022-06-13 · CVSS: 9.8 · CVSS 3.1

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.

Original CVE JSON · STIX 2.1

Source: CVE Program · Revision 8b16575c39f1e1810c5e863010da073d2d3285e7