datAInsights CVE Current

CVE-2021-35533 — Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an …

Published: 2021-11-26 · CVSS: 7.5 · CVSS 3.1

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

Original CVE JSON · STIX 2.1

Source: CVE Program · Revision 8b16575c39f1e1810c5e863010da073d2d3285e7